Academic Journal

Analysis of PT Interturn Short Circuit Fault in a Generator Outlet

التفاصيل البيبلوغرافية
العنوان: Analysis of PT Interturn Short Circuit Fault in a Generator Outlet
المؤلفون: Huijuan LIU, Yingming WANG, Li SU
المصدر: 发电技术, Vol 39, Iss 5, Pp 462-465 (2018)
بيانات النشر: Editorial Department of Power Generation Technology, 2018.
سنة النشر: 2018
المجموعة: LCC:Production of electric energy or power. Powerplants. Central stations
LCC:Science
مصطلحات موضوعية: generator outlet pt, interturn short circuit, zero sequence voltage, Applications of electric power, TK4001-4102, Production of electric energy or power. Powerplants. Central stations, TK1001-1841, Science
الوصف: Cabinet A and cabinet B of generator protection group of a power plant respectively reported "protection action of stator zero sequence high voltage section", which caused unit trip. It was found that the generator outlet potential transformer(PT) B phase 5042PT was obviously overheated. The accident process, through the breakdown PT finish straight resistance, insulation, excitation characteristic curve, and no-load current test, PT interturn short circuit are the main reasons of the unit tripping. In view of how to find early export PT insulation fault, the corresponding measures to prevent cracking was proposed. Specification requirements must be strictly according to the forecast to complete generator export PT partial discharge, triple frequency withstand voltage test, etc. In addition, the trend analysis was carried out on the data of various routine pre-test projects to detect the abnormality timely. The analysis of PT turn-to-turn short circuit fault at the generator outlet plays a good role in finding out the safety hidden danger and improving the reliability of the equipment. The regular completion of relevant tests in accordance with the standard requirements and the emphasis on the trend analysis of test data can effectively reduce the occurrence probability of the same type of accidents and reduce the scope of accidents.
نوع الوثيقة: article
وصف الملف: electronic resource
اللغة: English
Chinese
تدمد: 2096-4528
Relation: https://www.pgtjournal.com/EN/10.12096/j.2096-4528.pgt.2018.071; https://doaj.org/toc/2096-4528
DOI: 10.12096/j.2096-4528.pgt.2018.071
URL الوصول: https://doaj.org/article/eff7afe4ac18413a97e61fd4d2003d7f
رقم الانضمام: edsdoj.ff7afe4ac18413a97e61fd4d2003d7f
قاعدة البيانات: Directory of Open Access Journals
الوصف
تدمد:20964528
DOI:10.12096/j.2096-4528.pgt.2018.071