An improved fault control strategy for virtual synchronous generator with the coordination of STATCOM during unbalanced fault

التفاصيل البيبلوغرافية
العنوان: An improved fault control strategy for virtual synchronous generator with the coordination of STATCOM during unbalanced fault
المؤلفون: Yu Wang, Liang Ji, Yifan Ding, Xiao Chang, Qiteng Hong, Botong Li, Zhenkun Li, Xingwu Yang
المصدر: IET Generation, Transmission & Distribution, Vol 17, Iss 14, Pp 3245-3254 (2023)
بيانات النشر: Wiley, 2023.
سنة النشر: 2023
المجموعة: LCC:Production of electric energy or power. Powerplants. Central stations
مصطلحات موضوعية: control system analysis, power system control, Distribution or transmission of electric power, TK3001-3521, Production of electric energy or power. Powerplants. Central stations, TK1001-1841
الوصف: Abstract The virtual synchronous generator (VSG) is a good solution for stabilizing the power system with high penetration of renewable energy. However, in case of serious unbalanced voltage disturbance/fault, the conventional VSG may lose voltage, inertia, and damping support characteristics to the grid and even can cause disconnection of renewable energy. This paper proposes an improved fault control strategy for VSG with the coordination of STATCOM. The proposed method can provide sufficient voltage support while keeping continuous system inertia and damping support under severe unbalanced fault. In the paper, an improved VSG and STATCOM control topology based on positive and negative sequence current control are first proposed so as to keep the damping and inertia support to grid during the grid fault. Secondly, the voltage support control method for the VSG with improved topology during unbalanced fault is introduced, which can achieve multiple control objectives, in terms of voltage support, current limitation, and active power output simultaneously. Then a coordination control scheme of improved VSG and STATCOM is developed so as to optimize the maximum control objectives in all possible scenarios, especially in the case of severe unbalanced fault. Finally, the effectiveness of the method is verified by using the MATLAB/SIMULINK simulation platform.
نوع الوثيقة: article
وصف الملف: electronic resource
اللغة: English
تدمد: 1751-8695
1751-8687
Relation: https://doaj.org/toc/1751-8687; https://doaj.org/toc/1751-8695
DOI: 10.1049/gtd2.12896
URL الوصول: https://doaj.org/article/5b17a3b5ca4f497c96734dd05f2495b5