The issues of increasing the sensitivity and reliability of multi-parameter relay protection by sharing more than one information feature (current module, voltage module and phase, active and reactive power) are considered. In this case, the response parameters of individual one-dimensional measuring fault detectors based on the accumulation of statistical data during simulation in the Matlab / Similink software package are determined. A method for combining the signals of one-dimensional measuring fault detectors to increase the sensitivity of protection is proposed. The reliability of the organization of the logical part of multi-parameter relay protection was estimated using the theory of Markov processes, the principles of “2 out of 3” and “1 out of 2”.